Your Search returned 55 Results In 0.015 seconds
AC Ammeters, D72SD, D72

For full specification Click Here
NORTONICS MOVING IRON AC AMMETERS TYPES D48SD, D72SD & D96SD

 Accuracy:
Class 1.5
 Burden:
1A & 5A movements 0.7VA
6A to 30A movements 1.2VA
40A movements and above 2.4VA
 Ranges:
1/1.5/2/2.5/4/5/6/l0/15/20/25/30/40/50/60/80/l00Amps (D48SD only up to 40A)
1A & 5A movements also used as CT input ie, D72SD/CT5-100x6
 Overscales:
British standard x6. On request x2, x5 or no overscale
AC Ammeters
Din 48,72 & 96,

For full specification Click Here
Nortonics Square Din Switchboard Instruments

The Nortonics range of Din standard analogue meters are available in both 48mm, 72mm and 96mm. The moving iron ammeters are fitted with the British standard x6 overload scale. However x5, x2 and no overload options are also readily available. The Nortonics range as standard are supplied with 90 movements, 240 movements are alsoavailable to order - please contact the Nortonics sales office.
Analogue Meters
Display Meter with Relay and Signal Outputs, Cs1, digital display, microprocessor

For full specification Click Here

5 digit microprocessor meter with relay outputs, analogue signal output, RS485 Din 96x48mm 5 digit digital panel meters, available with a wide choice of both DC and AC inputs, along with many process inputs. The meter can be specified with a choice of one of three outputs, one relay (non adjustable from the front) can be specified as latched or non latched, an isolated analogue output or RS485 MODBUS RTU. The meter utilises the latest microprocessor technology in both the setting and operation of the meter.

CS1
DC Ampere Hour Meter with Relay and Signal Outputs, digital display, CS2, CS2-tM

For full specification Click Here

DC Ampere hour meter with relay outputs, analogue output, RS485 A Din 96x48mm DC Ampere Hour meter, taking a current reference from a DC shunt and integrating this reference against time to achieve an Ampere Hour or Ampere Minute reading. There are two display screens, the main ten digit screen is the totaliser display, the other screen is a "Batch" programmable setting. The meter can be specified with up to four relay outputs (2C/O and 2N/O) which can be assigned at the time of ordering for many functions to control say an electroplating system. As an option RS485 MODBUS is also available. Three volt free control inputs are featured as standard for functions such as reset.

CS2-TM
Miniature 48x24mm 3.5 Digit Microprocessor Display Meter with Relay and Signal Outputs, CS3

For full specification Click Here

Din 48x24 digital microprocessor meter with relay outputs, analogue signal output, RS485 Miniature Din 48x24mm 5 digit panel meters, available with a wide choice of DC analogue voltage and current signal inputs, along with potentiometer and resistance inputs. These meters can be specified with one or two relay outputs, plus if required an analogue output or RS485 MODBUS RTU. An excitation supply of 24VDC max 30mA is featured as standard on the CS3-PR version. These meters utilise the latest microprocessor technology in both the setting and operation of the meter.

CS3
Panel Meter for display of Amp Volt and Frequency, 3.5 Digit 0-1999 display, csm321, csm-321, digital display

For full specification Click Here

3� Digit panel meter  Measuring DCA, DCV, ACA, ACV, Hz  Accuracy DC: �0.1%, AC: �0.2%  3� Digital display : 1999  Peak Hold function (option)  Easy to wire, screw type terminal  DIN standard 96x48mm  High stability & low cost

CSM-321
Panel Meter for display of Amp Volt and Frequency, CSM421, CSM-421, 0-19999 display,

For full specification Click Here
4 Digit panel meter

 Measuring DCA, DCV, ACA, ACV, Hz
 Accuracy DC: 0.04%, AC: 0.1%
 4 Digital display: 19999
 Easy to wire, screw type terminal
 1/8 DIN standard (96x48mm)
 High stability & low cost
CSM-421
Miniature 48x24mm 3.5 Digit Display Meter, CSMS, CSMS321, CSMS-321, digital display

For full specification Click Here

Din 48x24mm 3� digit panel meter  Measuring DCA, DCV, ACA, ACV, Temperature  Accuracy �0.1% DC: �0.25% AC  0.2% (Pt100): �1% (K, J Thermocouple)  3� Digital display : 1999  1/32 DIN (48 x 24mm)  High stability & low cost

CSMS-321
Process Meter for display of mA mV VDC and Potentiometer Signals, 3.5 Digit 0-1999 display, CSR321, CSR-321, digital display

For full specification Click Here

3� Digit process meter  Measuring Process Signals; mA, Vdc,  Potentiometer, Pulse/u.  Accuracy �0.1%  3� Digital display : 1999  Easy to wire, screw type terminal  1/8 DIN standard (96 x 48mm)  High stability & low cost

CSR-321
Process Meter for display of mA mV VDC and Potentiometer signals, 0-19999 display, CSR421, CSR-421, digital display

For full specification Click Here

4� Digit process meter  Measuring Process Signals mA, Vdc,  Potentiometer, Pulse/u.  Accuracy �0.04%  4� Digital display: 19999  Easy to wire, screw type terminal  1/8 DIN standard (96 x 48mm)  High stability & low cost

CSR-421
Display Meter with Relay Outputs, 4 Digit 0-19999 display, CSS40, CSS-40, digital display

For full specification Click Here

Relay output trip meters 4 digit type (9999) A Din 96x48mm digital panel meter available in a 4 digit option with either one or two relay setpoint outputs. If one output is ordered this can be designated as a Low or High output in the ordering and in the case of two relay outputs Low/Low, High/High, High/Low. Also an extra output is provided as a Go output. This meter combines the traditional but popular user friendly front panel thumbwheel type push button switches to set the setpoints with the latest microprocessor technology.

CSS-40
Display Meter with Relay Outputs 4.5 Digit 0-19999 display, CSS41, CSS-41, digital display

For full specification Click Here

Relay output trip meter 4� digit type (19999) A Din 96x48mm digital panel meter available in a 4� digit option with either one or two relay setpoint outputs. If one output is ordered this can be designated as a Low or High output in the ordering and in the case of two relay outputs Low/Low, High/High, High/Low. Also an extra output is provided as a Go output. This meter combines the traditional but popular user friendly front panel thumbwheel type push button switches to set the setpoints with the latest microprocessor technology.

CSS-41
Display Meter with Relay Outputs, 5 Digit 0-99999 display, CSS50, CSS-50, digital display

For full specification Click Here

Relay output trip meters 5 digit type (99999) A Din 96x48mm digital panel meter available in a 5 digit option with either one or two relay setpoint outputs. If one output is ordered this can be designated as a Low or High output in the ordering and in the case of two relay outputs Low/Low, High/High, High/Low. Also an extra output is provided as a Go output. This meter combines the traditional but popular user friendly front panel thumbwheel type push button switches to set the setpoints with the latest microprocessor technology.

CSS-50
Temperature Display Meter, CST-321, CST321, digital display

For full specification Click Here

3� Digit temperature meter  Measuring T/C: K,J,T,E,R RTD: PT100  Accuracy �0.2% (T/C) �0.1% (PT100)  3� Digital display : 1999  Easy to wire, screw type terminal  DIN standard (96x48mm)  High stability & low cost

CST-321
6 Channel Temperature Display Meter, CST321M, CST-321M, digital display

For full specification Click Here

3� Digit six channel temperature meter  Measuring T/C: K,J,T,E,R RTD: PT100  Accuracy T/C:�0.25%, RTD:�0.1%  3� Digit display : 1999  Easy to wire, screw type terminal  DIN standard (96x48mm)  High stability & low cost

CST-321M
KWh meters CUBE 300 , CUBE-300, MODBUS, DUAL TARIFF,

For full specification Click Here

A Din 96mm digital KWh meter with a pulse output for interfacing with BMS systems. The CUBE 300 is suitable for single phase and three phase loads, both 3 wire and 4 wire balanced or unbalanced. The meter is designed to measure accurately all types of loads inductive or resistive and electronically controlled loads. The CUBE 300 benifits from fully isolated current inputs and to aid commissioning the meter can also display instantaneous KW for 60 seconds before reverting back to KWh. A high speed internal RS485 MODBUS communications option allows all readings to be given remotely. Also available is a Dual Tariff option giving two registers, tariff changeover is effected by an external input signal. NOTE: the CUBE 300 is available in standard execution ie, 400/415V L-L and 230VAC aux supply with 5Amp CT inputs. Non standard input voltages such as 110V L-L and 1Amp CT inputs are only available for large quantities. For smaller quantities please use the KWH CUBE.

CUBE 300
Multifunction metering Cube 350, cube350, cube-350/485, KWh, volts, amps, power factor, KW, KVArh, frequency, Modbus, Harmonics, RS485

For full specification Click Here

A Din 96mm digital electronic multifunction energy meter with dual pulse outputs as standard for interfacing with BMS systems. The CUBE 350 is equally suitable for single phase and three phase loads, both 3 wire or 4 wire balanced or unbalanced. The meter is designed to measure accurately all types of loads inductive or resistive and electronically controlled loads. The CUBE 350 benefits from fully isolated current inputs and to aid commissioning the meter also has fitted three "phase indicator lights" on the front of the meter. A high speed internal RS485 MODBUS communications option allows all displayed information plus additional information (see specifications below) to be read remotely. Also available is a Harmonics option, this information is obtained via the RS485 MODBUS. NOTE, the CUBE 350 is available in standard executions ie, 400/415V L-L and 230VAC aux supply with 5Amp CT inputs. Non standard input voltages such as 100V L-L and 1Amp CT inputs are only available for large quantities. For smaller quantities please use the MULTICUBE range.

CUBE 350
Multifunction metering CUBE 400, CUBE-400, volst, amps, power factor, kw, Kwh, KVar , frequency, Peak, export, Modbus, harmonics, RS485

For full specification Click Here

A Din 96mm digital three line backlit display electronic multifunction energy meter with dual pulse outputs as standard for interfacing with BMS systems. The CUBE 400 is equally suitable for single phase and three phase loads, both 3 wire or 4 wire balanced or unbalanced. The meter is designed to measure accurately all types of loads inductive or resistive and electronically controlled loads. As standard the meter also reads KWh, KVAh, KVArh as import and KWh & kVArh as export. The CUBE 400 benefits from fully isolated current inputs. A high speed internal R8485 MODBUS communications option allows all displayed information to be read remotely. Also available is a Harmonics option this is available both on the standard meter or with the RS485 MODBUS option. NOTE: the CUBE 400 is available in standard executions ie, 400 / 415V L-L and 230VAC aux supply with 5Amp CT inputs. Non standard input voltages such as 110V L-L and 110VAC auxiliary supplies, plus 1Amp CT inputs are only available for large quantities. For smaller quantities please use the MULTICUBE range.

CUBE 400
DC Ammeters, D48MC, D72MC, D96MC

For full specification Click Here
NORTONICS MOVING COIL DC AMMETERS
Types: D48MC, D72MC, D96MC
 Accuracy: Class 1.5
 Burden: 80mV to 150mV volt drop depending on input current
 Ranges: Any input between 50 to 800uA and 1 to 800mA
Also 1/1.5/2/2.5/4/5/6/10/15/20/25/30/40/50A
Dedicated 4-20mA version (D48MC only up to 30A)
 Scales: Special scales made as required
DC Ammeters
DC Shunts, UA-SHT

For full specification Click Here

TYPE A  Primary current 10 Amps to 200 Amps TYPE B  Primary current 200 Amps to 600 Amps TYPE C  Primary current 800 Amps to 2000 Amps TYPE D  Primary current 3000 Amps to 5000 Amps ALL TYPES  Standard accuracy �-1% (0.5% & 0.25% on request)  Specify with model the secondary: 50mV, 60mV 75mV, 100mV

DC Shunts
MID, kwh, Direct Connected KWHr meters, EEM12-32A, EEM, EEM34-3x65A, EEM34D, EM34D

For full specification Click Here

 Features  Din Rail Mounting  Suitable for Consumer Unit Mounting  3 Phase & 1 Phase Versions  Direct Connected no CTs Required  Most Units with Pulse Output

Direct Connected KWhr meters
FOX.SUM, FOXSUM, FOX SUM, FOX-SUM, FOX_SUM, summation, CT, CTS,

For full specification Click Here

Din rail mounted summation current transformers enable the summing of several independent loads on different supplies.

FOX.SUM
FOX.WP, FOXWP, FOX WP, FOX-WP, FOX_WP, WSK40, CT, CTS, current transformers, 1/1a, 1/5a, 5/1a, 5/5a, 10/1a, 10/5a, 15/1a, 15/5a, 20/1a, 20/5a, 25/1a, 25/5a, 30/1a, 30/5a, 40/1a, 40/5a

For full specification Click Here

Moulded case Primary Wound current transformers for primary currents from 1 Amp to 40 Amps. With built in terminal covers and M6 terminals for the primary current connection.

FOX.WP
FOX100.3, FOX.100.3, FOX 100.3, FOX-100.3, FOX_100.3, ASK103.3, CT, CTS, current transformers, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/5a, 2000/5a, 2500/5a, 3000/5

For full specification Click Here

Moulded case compact current transformer, for primary currents from 400 Amps to 4000 Amps.  With built-in sliding sealable terminal covers.

FOX100.3
FOX100.55, FOX.100.55, FOX 100.55, FOX-, CT, CTS, current transformers, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a, 2500/1a, 2500/5a, 3000/1a, 3000/5a, 4000/1a, 4000/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 600 Amps to 4000 Amps.  With built-in sliding sealable terminal covers.

FOX100.55
FOX105, FOX.105, FOX 105, FOX-105, FOX_105, CT, CTS, current transformers, 100/1a, 100/5a, 150/1a, 150/5a, 200/1a, 200/5a, 250/1a, 250/5a

For full specification Click Here

Moulded case "triple" current transformer, with apertures on 35mm centres, giving an overall width of 105mm allowing installation directly on top of moulded case circuit breakers.

FOX105
FOX105.38, FOX.105.38, FOX-105.38, FOX_105.38, ASK128.4, CT, CTS, current transformers, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a, 2500/1a, 2500/5a, 3000/1a, 3000/5a, 4000/1a, 4000/5a

For full specification Click Here

Moulded case compact current transformer, for mounting on vertical bus-bars with primary currents from 800 Amps to 4000 Amps.  With built-in sliding sealable terminal covers.

FOX105.38
FOX127.38, FOX.127.38, FOX-127.38, FOX_127.38, CT, CTS, current transformers, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a, 2500/1a, 2500/5a, 3000/1a, 3000/5a, 4000/1a, 4000/5a, 5000/1a, 5000/5a

For full specification Click Here

Moulded case compact current transformer, for mounting on vertical bus-bars with primary currents from 800 Amps to 5000 Amps.  With built-in sliding sealable terminal covers.

FOX127.38
FOX127.54, FOX.127.54, FOX 127.54, FOX-127.54, FOX_127.54, ASK129.10, CT, CTS, current transformers, 3000/1a, 3000/5a, 4000/1a, 4000/5a, 5000/1a, 5000/5a, 6000/1a, 6000/5a

For full specification Click Here

Moulded case compact current transformer, for mounting on vertical bus-bars with primary currents from 3000 Amps to 6000 Amps.  With built-in sliding sealable terminal covers.

FOX127.54
FOX140, FOX.140, FOX 140, FOX-140, FOX_140, CT, CTS, current transformers, 250/1a, 250/5a, 300/1a, 300/5a, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a

For full specification Click Here

Moulded case "triple" current transformer, with apertures on 45mm centres, giving an overall width of 140mm allowing installation directly on top of moulded case circuit breakers.

FOX140
FOX21, FOX.21, FOX 21, FOX-21, ASR20.3, FOX_21, CT, CTS, current transformers, 50/1a, 50/5a, 60/1a, 60/5a, 80/1a, 80/5a, 100/1a, 100/5a, 150/1a, 150/5a, 200/1a, 200/5a, 250/1a, 250/5a, 300/1a, 300/5a

For full specification Click Here

Moulded case compact "our smallest current transformer" for primary currents from 50 Amps to 300 Amps. comes with built in sliding sealable terminal covers.

FOX21
FOX30.1, FOX.30.1, FOX 30.1, FOX-30.1, FOX_30.1, ASK31.3, ASK318.3, CT, CTS, current transformers, 100/1a, 100/5a, 150/1a, 150/5a, 200/1a, 200/5a, 250/1a, 250/5a, 300/1a, 300/5a, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 100 Amps to 600 Amps.  With built-in sliding sealable terminal covers.

FOX30.1
FOX40.1, FOX.40.1, FOX 40.1, FOX-40.1, FOX_40.1, ASK41.3, ASK412.4, CT, CTS, current transformers, 100/1a, 100/5a, 150/1a, 150/5a, 200/1a, 200/5a, 250/1a, 250/5a, 300/1a, 300/5a, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 100 Amps to 800 Amps.  With built-in sliding sealable terminal covers.

FOX40.1
FOX50.1, FOX.50.1, FOX 50.1, FOX-50.1, FOX_50.1, ASK561.4, ASK51.4, ASK541.4, CT, CTS, current transformers, 250/1a, 250/5a, 300/1a, 300/5a, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 250 Amps to 1200 Amps.  With built-in sliding sealable terminal covers.

FOX50.1
FOX60.15, FOX.60.15, FOX 60.15, FOX-60.15, FOX_60.15, ASK61.4, ASK63.4, ASK63.6, CT, CTS, current transformers, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 400 Amps to 1600 Amps.  With built-in sliding sealable terminal covers.

FOX60.15
FOX60.3, FOX.60.3, FOX 60.3, FOX-60.3, FOX_60.3, ASK63.6, CT, CTS, current transformers, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 400 Amps to 2000 Amps.  With built-in sliding sealable terminal covers.

FOX60.3
FOX.75, FOX75, FOX 75, FOX-75, FOX_75, CT, CTS, current transformers, 60/1a, 60/5a, 100/1a, 100/5a, 150/1a, 150/5a

For full specification Click Here

Moulded case "triple" current transformer, with apertures on 25mm centres, giving an overall width of 75mm allowing installation directly on top of moulded case circuit breakers.

FOX75
FOX80.1, FOX.80.1, FOX 80.1, FOX-80.1, FOX_80.1, ASK81.4, CT, CTS, current transformers, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a

For full specification Click Here

Moulded case compact current transformer, for primary currents from 400 Amps to 2000 Amps.  With built-in sliding sealable terminal covers.

FOX80.1
FOX84.34, FOX.84.34, FOX84-34, CT, CTS, current transformers, 400/1a, 400/5a, 500/1a, 500/5a, 600/1a, 600/5a, 800/1a, 800/5a, 1000/1a, 1000/5a, 1200/1a, 1200/5a, 1500/1a, 1500/5a, 1600/1a, 1600/5a, 2000/1a, 2000/5a, 2500/1a, 2500/5a

For full specification Click Here

Moulded case compact current transformer, for mounting on vertical bus-bars with primary currents from 400 Amps to 2500 Amps.  With built-in sliding sealable terminal covers.

FOX84.34
Frequency Meters, D48HZ, D72HZ, D96HZ

For full specification Click Here
NORTONICS FREQUENCY METERS
Types: D48HZ, D72HZ, D96HZ
Accuracy: Class 1
Burden: 6mA
Ranges: 45-55Hz, 45-65Hz, 55-65Hz, 360-440Hz
(45-65Hz standard range) Supply voltage
must also be specified 110/240/380/415/440V
Frequency Meters
KWh meters KWH CUBE, KWhr Cube, KWH-CUBE, ND

For full specification Click Here
A Din 96mm digital KWh meter with pulse output for interfacing with BMS systems. One unit suitable for both single phase and three phase 3 wire or 4 wire loads, balanced or un-balanced. The meter benefits from fully isolated current inputs and to aid commissioning instantaneous KW can be displayed to confirm the load to be measured. The meter not only being in the popular Din 96mm size is only 71mm deep. Utilising the latest backlit display technology affords excellent viewing visibility.
KWH-CUBE
KWh meters M600, KWh, KWh meter

For full specification Click Here
A Din 96mm KWh meter that is designed to compliment standard panel instruments. Available in both single phase, three phase balanced or unbalanced, 3 wire or 4 wire configuration. Also available is a DC KWh meter option, meter type EL96GT. All meters can be supplied with or without volt free relay pulse output, standard pulse rate 1 pulse per KWh (other pulse rates upon request). Front panel LED flashes every 0.1KWh. The counter is a 7 digit mechanical non resettable type.
M600
MID, kwh, Direct Connected KWHr meters, EEM12-32A, EEM, EEM34-3x65A, EEM34D, EM34D,  schell

For full specification Click Here

MID stands for �Measuring Instruments Directive" and is a new European Union directive to create a single market for measuring instruments across the EU and was effective from the 30th October 2006. The aim of the directive is to guarantee to users a standard European level of safety, reliability, tamper proofing and accuracy to instruments. For when meters are subjected to certain minimum specified levels of climatic conditions, mechanical environments and electromagnetic interference. "MID" is a replacement for the old UK "OFGEM" approval, also referred to sometimes as "OFFER" approval. It is advised that all electricity meters must be approved if used in a billing situation. This is a requirement of Schedule 7 of the Electricity Act 1989. Prior to the 30th October 2006 approval would have been granted by OFGEM. However, meters approved under previous UK provisions need not be certified in exempt situations. Usually landlord/tenant contracts, so long as a written agreement exists between the parties to dispense with the certification requirements. But any meter must still be of an approved design and be maintained in good working order. The new MID directive refers to ten categories of measuring instruments of which four relate to utility meters. In particular KWh meters fall within MI-003 ACTIVE ELECTRICAL ENERGY METERS.

MID KWh Meter
cos, Power Meter with Relay and Signal Outputs, Digital Power Factor Meter, MPF5, MPF-5, digital display

For full specification Click Here

4� Digit power meter with relay outputs, analogue signal output, RS485 Din 96x48mm digital single parameter power meters either as Watts, VAR or Power Factor. The meters can be specified for both single and three phase systems, 3 or 4 wire and are suitable for both balanced and unbalanced loads. The meters can be specified as a "display only" meter, or with a choice of one or two outputs. One relay or two relays that can be specified as latched or non latched, or an isolated analogue output with or without one relay output. Or with, or without RS485 MODBUS RTU which can also be with or without one relay output. The meter utilises the latest microprocessor technology in both the setting and operation of the meter.

MPF-5 (COS)
VAR, Power Meter with Relay and Signal Outputs, Digital VAR Meter, MQ5, MQ-5, digital display

For full specification Click Here

4� Digit power meter with relay outputs, analogue signal output, RS485 Din 96x48mm digital single parameter power meters either as Watts, VAR or Power Factor. The meters can be specified for both single and three phase systems, 3 or 4 wire and are suitable for both balanced and unbalanced loads. The meters can be specified as a "display only" meter, or with a choice of one or two outputs. One relay or two relays that can be specified as latched or non latched, or an isolated analogue output with or without one relay output. Or with, or without RS485 MODBUS RTU which can also be with or without one relay output. The meter utilises the latest microprocessor technology in both the setting and operation of the meter.

MQ-5 (VAR)
Multifunction metering multicube, multi-cube, multi cube,

For full specification Click Here
A DIN 96mm x 96mm LCD multi display meter and only 71mm deep
available in six different permutations.

 Features
One Meter Measures ALL your values. Economically replaces Ammeters, Voltmeters, Switches, PF & kW Indicators, kWh Meters etc.
Easy to See. Clear Backlit LCD Display with a Very Wide Viewing Angle
Easy to Use. Four Keys select all parameters
Safe to Use. Fully Isolated Current Inputs for Complete User & Installation Safety - Complies with the Low Voltage Directive (LVD)
Small in Size yet great in Performance. Needs Only 71mm behind the panel - Measures every single cycle up to the 20th Harmonic
Simple to Install. Software Detection/Correction of Wiring Errors
Multicube
Power Meter with Relay and Signal Outputs, Digital Watt Meter, MW-5, MW5, digital display

For full specification Click Here

4� Digit power meter with relay outputs, analogue signal output, RS485 Din 96x48mm digital single parameter power meters either as Watts, VAR or Power Factor. The meters can be specified for both single and three phase systems, 3 or 4 wire and are suitable for both balanced and unbalanced loads. The meters can be specified as a "display only" meter, or with a choice of one or two outputs. One relay or two relays that can be specified as latched or non latched, or an isolated analogue output with or without one relay output. Or with, or without RS485 MODBUS RTU which can also be with or without one relay output. The meter utilises the latest microprocessor technology in both the setting and operation of the meter.

MW-5 (WATT)
Phase Sequence Indicators, PSI. FE72

For full specification Click Here
Phase Sequence Indicators

Nortonics Phase Sequence Indicators (P.S.I.) are suitable for a range of applications to indicate both the presence of all three phases and the correct sequence of those phases.

Incorrect phase connection will often cause serious damage to the motors of compressors, pumps, gen-sets, heating and ventilation equipment. Mobile generators, remote installations and shore to ship supplies are most vulnerable to such hazzards and are, therefore, ideal applications for Nortonics range of P.S.I.

The absence of a phase is indicated by and a neon and the missing phase is identified. The presence of all three phases in the correct sequence is indicated by the white neon. Incorrect phase sequence is indicated by a red neon.
Phase Sequence Indicator
power factor, D96PF

For full specification Click Here
NORTONICS POWER FACTOR METER
Type: D96PF (Self contained)
Accuracy: Class 1.5
Burden: Current inputs 0.5VA, voltage inputs 2VA
Inputs: Current via 1Amp or 5Amp CT input
Voltage direct 63VAC to 500VAC
System: 3P3W Balanced
Range: CAP 0.5 to 1 to IND 0.5
Power Factor Meters
Multifunction metering Powerrail 350, volts, amps, power factor, kw, kwh, kvar, peak, modbus, harmonics, rs485

For full specification Click Here

A Din rail mounted digital electronic multifunction energy meter with dual pulse outputs as standard for interfacing with BMS systems, the meter also is suitable for consumer unit mounting. The POWER RAIL 350 is equally suitable for single phase and three phase loads, both 3 wire or 4 wire balanced or unbalanced. The meter is designed to measure accurately all types of loads inductive or resistive and electronically controlled loads. The POWER RAIL 350 benefits from fully isolated current inputs. A high speed internal RS485 MODBUS communications option allows all displayed information plus additional information to be read remotely. Also available is a Harmonics option this information is obtained via the RS485 MODBUS.

Powerrail 350
KWh meters Power rail, powerrail, powerail, 303, PR303, KWh, KWh meter

For full specification Click Here

The Power Rail 303 is a single function electronic kWh meter. Standard current transformer inputs (CTs) allow connection to loads of a few watts to hundreds of megawatts. Accurate measurements of kWh provide repeatable results required by energy management schemes. Designed for ease of installation, the Power Rail 303 has quality rising cage terminals which allow repeated use and secure termination of a wide range of cable types and sizes. An isolated pulse output is available in the form of a volt free contact pair (relay switch). The contacts close for 100msec each time the LCD kWh counter increments. This output is suitable for direct connection to Building Energy Management Systems (BEMS). A high speed internal RS485 MODBUS communications option allows all readings to be read remotely. Also available is a KW Maximum Demand option, available with or without the MODBUS option.

PR303
Shunts, UA-SHT, DC

For full specification Click Here

TYPE A  Primary current 10 Amps to 200 Amps TYPE B  Primary current 200 Amps to 600 Amps TYPE C  Primary current 800 Amps to 2000 Amps TYPE D  Primary current 3000 Amps to 5000 Amps ALL TYPES  Standard accuracy �-1% (0.5% & 0.25% on request)  Specify with model the secondary: 50mV, 60mV 75mV, 100mV

Shunts
DC Multi Display Power Meter, VAW, digital display, rs485

For full specification Click Here

DC Multi display power meter with relay outputs, analogue signal output, RS485 A Din 96x48mm multi display DC power meter. Measuring, displaying and communicating DC voltage, current, instantaneous power (Watts/KW), import and export Wh/KWh along with hours run. The voltage, current and power parameters also have max and min value recording during power on. The meter has the possibility for specifying up to 4 relay outputs including pulse outputs. The relays can be determined as set points for any of the parameters either low or high. In addition an analogue output also can be requested which can be assigned to any of the instantaneous measured parameters. Lastly, along with all the above mentioned outputs, RS485 MODBUS RTU communications can also be specified. The VAW meter is particularly suitable for solar energy and wind energy systems, along with electroplating, battery and transport applications. A particular feature of this meter which is especially relevant in "green energy" applications, is that after a certain time of no operator interaction with the meter, the meter enters a "switch down" mode and reduces the power to the LEDs, thus saving money.

VAW
Voltmeters, D72SD, D48SD, D96SD

For full specification Click Here
NORTONICS MOVING IRON AC VOLTMETERS
Types: D48SD, D72SD, D96SD
Accuracy: Class 1.5
Burden : Max 6VA
Ranges: 150/300/600VAC
Voltmeters
watt meters, D96WA

For full specification Click Here
NORTONICS WATTMETERS
Type: D96WA (Self contained)
Accuracy: Class 1.5
Burden: Current inputs 0.5VA, voltage inputs 2VA
Inputs: Current via 1Amp or 5Amp CT input
Voltage direct 63VAC to 500VAC
Systems: Single phase
3P3W Balanced - 3P4W Balanced - 3P3W Unbalanced - 3P4W Unbalanced
Watt meters