Voltage Control Relays,Signal Control Relays and Trip Amplifiers, Signal Control Relays & Trip Amplifiers, YWRU2T/10VDC,ADJUSTABLE DUAL SETPOINT, trip amp

For full specification Click Here
Dual setpoint 0.1-10V DC relay. Providing two separately controllable trip levels. With R1 selected as the "High" level and R2 as the "Low" level. When the monitored signal voltage rises above R2 set level R2 relay will energise. If the voltage continues to rise above R1 set level, relay R1 will energise. Conversely as the monitored voltagefalls R1 will de-energise, if the fall continues R2 will de-energise. The unit has a built in fixed hysteresis of 2% at each setpoint to avoid relay "chatter".
DUAL SETPOINT ADJUSTABLE 0.1-10V DC trip amp YWRU2T/1OVDC (2 x spco)
Signal Control Relays and Trip Amplifiers, Signal Control Relays & Trip Amplifiers, YWRU, YWRIT, 2002, 4002, 2002-ALM, 4002-ALM,2002 ALM, 4002 ALM

For full specification Click Here
 2002-ALM
 Dual trip amplifier, 12VDC to 24VAC supply voltages

 4002-ALM
 Dual trip amplifier, 24VDC to 240VAC supply voltages
Dual trip amplifier
Current Relays, TRIP AMP,  ywrit4, Signal Control Relays and Trip Amplifiers, Signal Control Relays & Trip Amplifiers,

For full specification Click Here
Current control for rising current link terminals Y2 & B1. The output relay energises when the monitored current signal rises above the set level selected via the front potentiometer. The output relay de-energises when the monitored current falls below the set level less the hysteresis adjustable via a second potentiometer, 5 to 50% against the set level. On initial start up (connection of the auxiliary supply), the output relay is inhibited for a time period adjustable between 0.1-10 secs, this allows the measuring circuit to correctly determine the level of the monitored current signal before operation.
Current control for falling current link terminals Y1 & Y2. The output relay de-energises when the monitored current signal rises above the set level selected via the front potentiometer. The output relay re-energises when the monitored current falls below the set level less the hysteresis adjustable via a second potentiometer, 5 to 50% against the set level. On initial start up (connection of the auxiliary supply), the output relay will energise for a time period adjustable between 0.1-10 secs, irrespective of the level of the monitored current signal.
TRIP AMP SELECTABLE FOR A RISING OR FALLING SIGNAL ywrit4
Current Relays, Signal Control Relays and Trip Amplifiers, Signal Control Relays & Trip Amplifiers, ywrit, 11writ, ywri2t, trip amps

For full specification Click Here
YWRIT - Din rail 1-20mA adjustable single setpoint trip amp.

11WRIT -11 pin plug in 1 -20mA adjustable single setpoint trip amp.

YWRI2T - Din rail 1 -20mA two adjustable setpoint trip amp 2 x SPCO outputs "Low" & "High"
trip amps 1-20ma dc ywrit 11writ ywri2t